Спецификация S8AS изготовлена ​​​​«Omron» и имеет функцию, называемую «Smart Power Supply».

Детали детали

Номер произв S8AS
Описание Smart Power Supply
Производители Omron
логотип Omron логотип 

26 Pages
scroll

No Preview Available !

S8AS Даташит, Описание, Даташиты
Smart Power Supply
S8AS
www.DataSheet4U.com
CSM_S8AS_DS_E_4_1
A New Type of Power Supply That
Provides Safety and Maintainability
• 240- and 480-W power supplies with and digital circuit
protectors in a single package.
• Each branch output tripping current value can be easily
set at 0.1-A increments.
• Startup and shutdown sequence control included.
• Various monitor displays and alarms (output voltage,
output current, maintenance forecast monitor,
temperature).
• Conforms to UL Class 2
• Mounts to DIN Rail.
Refer to Safety Precautions for All Power Supplies and Safety
Precautions on page 23.
Model Number Structure
Model Number Legend
S8AS-@@@@@@
1 23
1. Capacity
240: 240 W
480: 480 W
2. Number of Output Branches
06: 6 branch outputs
08: 8 branch outputs
3. Additional Functions
Blank: Changeable parameter settings with no communications
N: Unchangeable parameter settings with no communications
R: Changeable parameter settings with communications (RS-485)
Ordering Information
S8AS
Capacity Input voltage
Output
voltage
240 W
480 W
100 to
240 VAC
24 V
Maximum cutoff Total
output current output
(per branch) current
3.8 A
10 A
20 A
Number
of output
branches
Communications
functions
Parameter
settings
Model
6 branch
outputs
None
None
RS-485
Changeable S8AS-24006
Not changeable S8AS-24006N
Changeable S8AS-24006R
8 branch
outputs
None
None
RS-485
Changeable S8AS-48008
Not changeable S8AS-48008N
Changeable S8AS-48008R
Be sure to read and fully understand the content of the S8AS User's Manual (Cat. No. Z269) before changing settings on the S8AS.
1









No Preview Available !

S8AS Даташит, Описание, Даташиты
Specifications
S8AS
www.DataSheet4U.com
S8AS-24006@
Item
Model
S8AS-24006
S8AS-24006N
S8AS-24006R
Efficiency (Typ.)
80% min.
Voltage range *1
100 to 240 VAC (85 to 264 VAC)
Frequency *1
50/60 Hz (47 to 63 Hz)
Input
condi-
tions
Current
100-V input
200-V input
Power factor
Harmonic current
Leakage
current
100-V input
200-V input
3.8 A max.
2.0 A max.
0.95 min.
EN61000-3-2
0.5 mA max.
1.0 mA max.
Inrush current 100-V input
*2 200-V input
25 A max. (for a cold start at 25°C)
50 A max. (for a cold start at 25°C)
Number of branches
6
Maximum cutoff output current (per branch)
3.8 A
Total output current
10 A
Allowable voltage range *3
±10% (with V.ADJ)
Output
condi-
tions
Ripple noise voltage
Output leakage current
Input fluctuation
2.0% [P-P] max. (for rated input and output voltage) *4
10 mA max.
0.5% max. (Input: 85 to 264 VAC, 100% load) *5
Load fluctuation (rated input voltage)
4.0% max. (rated input, 0% to 100% load) *5
Temperature fluctuation
0.05%/°C max.
Startup time *2
3,000 ms max. (for rated input and output voltage) *4
Output hold time *2
20 ms max. (for rated input and output voltage) *4
Abnormal voltage tripping
28.8 V (Cannot be changed.)
Tripping
functions
Abnormal current tripping *2
Abnormal total current tripping
Setting range: 0.5 to 3.8 A
(in 0.1-A increments)
3.8 A (Cannot be changed.)
Setting range: 0.5 to 3.8 A
(in 0.1-A increments)
Branch outputs are cut off when the total output current is more than 17 A for 2 s, 15 A for 5 s, 13 A for 10 s, or 12 A for 20 s.
Tripping alarm output
Photoswitch output
30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max.
Undervoltage Undervoltage detection
detection
functions
Undervoltage detection output
Setting range: 18.0 to 26.4 V
(in 0.1-V increments)
20.0 V (Cannot be changed.)
Setting range: 18.0 to 26.4 V
(in 0.1-V increments)
Photoswitch output
30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max.
Maintenance
forecast
monitor
function
Maintenance forecast monitor
Maintenance forecast monitor
output
Setting range: 0.0 to 5.0 yr
(in 0.5-yr increments)
0.5 yr (Cannot be changed.)
Setting range: 0.0 to 5.0 yr
(in 0.5-yr increments)
Photoswitch output
30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max.
Over-
temperature
detection
function
Over-temperature
Over-temperature output
Setting range: 25 to 90°C
(in 1°C increments)
90°C (Cannot be changed.)
Setting range: 25 to 90°C
(in 1°C increments)
Photoswitch output
30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max.
Output voltage display
Display range:17.0 to 30.0 V
Display accuracy: 2% rdg ±1 digit max.
Func-
tions
Display
functions
Output current display
Maintenance forecast monitor
display
Branch output display range: 0.0 to 4.0 A
Peak output current display range: 0.0 to 20.0 A
Total current display range: 0.0 to 40.0 A
Display accuracy: 5% FS (4 A) ±1 digit max.
Display range: FUL (Full)/HLF (Half)/0.0 to 5.0 yr
Temperature display
Display range: 20 to 100°C
Display accuracy: 2°C ±1 digit max.
External Tripping Input
The input can be enabled or disabled for
each branch output.
19.2 to 30.0 VDC, minimum signal
width: 10 ms, tripping after input within
20 ms + the shutdown sequence set
time
All branch outputs: Enabled
(Cannot be changed.)
19.2 to 30.0 VDC, minimum signal
width: 10 ms, tripping after input within
20 ms + the shutdown sequence set
time
The input can be enabled or disabled for
each branch output.
19.2 to 30.0 VDC, minimum signal
width: 10 ms, tripping after input within
20 ms + the shutdown sequence set
time
Startup sequence
Setting range: 0.0 to 99.9 s in 0.1-s
increments
Branch output 1: 0.0 s
(Cannot be changed.)
Branch output 2: 0.4 s
(Cannot be changed.)
Branch output 3: 0.8 s
(Cannot be changed.)
Branch output 4: 1.2 s
(Cannot be changed.)
Branch output 5: 1.6 s
(Cannot be changed.)
Branch output 6: 2.0 s
(Cannot be changed.)
Setting range: 0.0 to 99.9 s in 0.1-s
increments
Shutdown sequence
Setting range: 0.0 to 99.9 s in 0.1-s
increments
All branch outputs: 0.0 s
(Cannot be changed.)
Setting range: 0.0 to 99.9 s in 0.1-s
increments
Communications
Not supported
Supported (RS-485)
Sampling period
1 ms
Parallel connection
Not supported
Series connection
Not supported
Note: Refer to the next page for information on *1 to *5.
2









No Preview Available !

S8AS Даташит, Описание, Даташиты
S8AS
www.DataSheet4U.com
Item
Model
S8AS-24006
S8AS-24006N
S8AS-24006R
Ambient operating temperature
Refer to the derating curve (no icing or condensation). *2
Storage temperature
25 to 65°C
Ambient operating humidity
25% to 85% (storage: 25% to 90%)
Withstand voltage
Others
Insulation resistance
3.0 kVAC for 1 min between all input terminals collectively and all branch output, all I/O signal, and all communications
terminals collectively (Detection current: 20 mA)
2.0 kVAC for 1 min between all inputs and protective earth (Detection current: 20 mA)
1.0 kVAC for 1 min between protective earth and all branch output, all I/O signal, and all communications terminals
collectively (Detection current: 20 mA)
500 VAC for 1 min between all branch output and all I/O signal/communications terminals collectively
(Detection current: 20 mA)
500 VAC for 1 min between all I/O signal terminals collectively and communications terminals collectively
(Detection current: 20 mA)
500 VAC for 1 min between all I/O signal terminals collectively and all output signal terminals collectively
(detection current: 20 mA)
100 MΩ min. at 500 VDC between the protective earth terminal or all input terminals collectively and all branch output,
all I/O signal, and all communications terminals collectively
Vibration resistance
No abnormality after 10 to 55 Hz at 0.375-mm single amplitude for 2 h each in 3 directions.
Shock resistance
No abnormality after 150 m/s2 3 times each in 6 directions.
Output indicator
Provided (Color: green)
Conducted EMI
Conforms to EN 61204-3 Class A and FCC Class A.
Radiated EMI
Conforms to EN 61204-3 Class A.
Safety standards
cULus: UL508 (Listing. Class2: Per UL1310), CSA C22.2 No.107.1 (Class2: Per CSA C22.2 No.22.3)
cURus: UL60950-1, CSA C22.2 No.60950-1
EN: EN50178, EN60950-1
VDE: VDE0160, VDE0805 Teil1
Weight
1,600 g max.
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*2. Refer to Engineering Data on page 8 for details.
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than 10% of the voltage adjustment range. When adjusting
the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged. If the output voltage
exceeds 28.8 V, all branch outputs will be cut off.
*4. Rated input and output conditions: Rated input voltage, rated frequency, rated output voltage, rated total output current, and maximum cutoff
output current.
*5. 100% load conditions: Rated output voltage, rated total output current, and maximum cutoff output current.
3










Скачать PDF:

[ S8AS.PDF Даташит ]

Номер в каталогеОписаниеПроизводители
S8A8 Amp Silicon Rectifier 50 to 1000 VoltsMicro Commercial Components
Micro Commercial Components
S8ASSmart Power SupplyOmron
Omron

Номер в каталоге Описание Производители
TL431

100 мА, регулируемый прецизионный шунтирующий регулятор

Unisonic Technologies
Unisonic Technologies
IRF840

8 А, 500 В, N-канальный МОП-транзистор

Vishay
Vishay
LM317

Линейный стабилизатор напряжения, 1,5 А

STMicroelectronics
STMicroelectronics

DataSheet26.com    |    2020    |

  Контакты    |    Поиск