DataSheet26.com

S8VK-G PDF даташит

Спецификация S8VK-G изготовлена ​​​​«Omron» и имеет функцию, называемую «Switch Mode Power Supply».

Детали детали

Номер произв S8VK-G
Описание Switch Mode Power Supply
Производители Omron
логотип Omron логотип 

22 Pages
scroll

No Preview Available !

S8VK-G Даташит, Описание, Даташиты
New Product
Switch Mode Power Supply
S8VK-G (15/30/60/120/240/480-W Models)
Reliable and Easy Operation-Worldwide Power Supply
Resistant in tough environments
Easy and fast installation
The most compact class on the market
• Universal input for worldwide applications:
100 to 240 VAC (85 to 264 VAC)
• DC input can be available: 90 to 350 VDC
• Possible for 2 phases input usage.
• Wide operation temperature range: –40 to 70 °C
• Power Boost function at 120%
• Safety standards:
UL508/60950-1, CSA C22.2 No. 107.1/60950-1
EN50178 (= VDE0160), EN60950-1 (= VDE0805).
Lloyd’s standards, EN60204-1 PELV
Safety of Power Transformers: EN61558-2-16
• 15-W,30-W, and 60-W models conform to
UL Class 2 output Standards
• EMS: EN 61204-3
EMI: EN61204-3 Class B
http://www.DataSheet4U.net/
!
Refer to Safety Precautions for All Power Supplies and Safety
Precautions on page 17.
1
datasheet pdf - http://www.DataSheet4U.net/









No Preview Available !

S8VK-G Даташит, Описание, Даташиты
S8VK-G
Model Number Structure
Model Number Legend
Note: Not all combinations are possible. Refer to List of Models in Ordering Information, below.
S8VK- @@@@@@
12 3
1. Input voltage types
G: Single phase
2. Power Ratings
015: 15 W
030: 30 W
060: 60 W
120: 120 W
240: 240 W
480: 480 W
3. Output voltage
05: 5 V
12: 12 V
24: 24 V
48: 48 V
Ordering Information
Note: For details on normal stock models, contact your nearest OMRON representative.
Power ratings
15 W
Input voltage
30 W
60 W
120 W
240 W
480 W
Single phase
100 to 240 VAC
90 to 350 VDC
Output Voltage
5V
12 V
24 V
5V
12 V
24 V
12 V
24 V
24 V
24 V
48 V
24 V
48 V
Output current
3A
1.2 A
0.65 A
5A
2.5 A
1.3 A
4.5 A
2.5 A
5A
10 A
5A
20 A
10 A
http://www.DataSheet4U.net/
Boost Current
3.6 A
1.44 A
0.78 A
6A
3A
1.56 A
5.4 A
3A
6A
12 A
6A
24 A
12 A
Model number
S8VK-G01505
S8VK-G01512
S8VK-G01524
S8VK-G03005
S8VK-G03012
S8VK-G03024
S8VK-G06012
S8VK-G06024
S8VK-G12024
S8VK-G24024
S8VK-G24048
S8VK-G48024
S8VK-G48048
2
datasheet pdf - http://www.DataSheet4U.net/









No Preview Available !

S8VK-G Даташит, Описание, Даташиты
S8VK-G
Specifications
Ratings, Characteristics, and Functions
Power ratings
15 W
30 W
Item
Output voltage
5V
12 V
24 V
5V
12 V
24 V
Efficiency (Typical)
230 VAC input
77%
80%
79%
82%
86%
Voltage *1
100 to 240 VAC, 90 to 350 VDC (allowable range: 85 to 264 VAC) *6
Frequency *1
50/60 Hz (47 to 450 Hz)
115 VAC input
Current (Typical)
230 VAC input
0.32 A
0.2 A
0.3 A
0.21 A
0.31 A
0.2 A
0.5 A
0.32 A
0.57 A
0.37 A
0.58 A
0.36 A
Input
Power factor
(Typical)
230 VAC input
Harmonic current emissions
0.42
Conforms to EN61000-3-2
0.43
0.42
0.43
Leakage current 115 VAC input
(Typical)
230 VAC input
0.14 mA
0.25 mA
0.13 mA
0.24 mA
Inrush current
(Typical) *2
115 VAC input
230 VAC input
16 A
32 A
Voltage adjustment range *3
–10% to 15% (with V.ADJ) (guaranteed)
Ripple *4
at 20 MHz (Typical) 60 mV
50 mV
30 mV
30 mV
30 mV
30 mV
Input variation influence
0.5% max. (at 85 to 264 VAC input, 100% load)
Output
Load variation Influence
(Rated Input voltage)
Temperature variation influence
3.0% max. (5 V), 2.0% max. (12 V), 1.5% max. (24 V), at 0% to 100% load
0.05%/°C max.
Start up time
(Typical) *2
115 VAC input
230 VAC input
530 ms
330 ms
520 ms
400 ms
580 ms
400 ms
550 ms
430 ms
550 ms
490 ms
600 ms
480 ms
Hold time
(Typical) *2
115 VAC input
230 VAC input
28 ms
134 ms
29 ms
138 ms
32 ms
134 ms
33 ms
177 ms
36 ms
170 ms
23 ms
154 ms
Overload protection *2
121% to 160% of rated load current (130% typ value)
Overvoltage protection *2
Additional
functions
Power Boost
Parallel operation
Yes *5
120% of rated current (Refer to Engineering Data)
Yes (Refer to Engineering Data)
Series operation
Possible for up to two Power Supplies (with external diode)
Ambient operating temperature
–40 to 70°C (Refer to Engineering Data)
Storage temperature
–40 to 85°C
http://www.DataSheet4U.net/
Ambient operating humidity
0% to 95% (Storage humidity: 0% to 95%)
Dielectric strength
(detection current: 20 mA)
3.0 kVAC for 1 min. (between all inputs and outputs)
2.0 kVAC for 1 min. (between all inputs and PE terminal)
1.0 kVAC for 1 min. (between all outputs and PE terminal)
Insulation resistance
100 Mmin. (between all outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min. each in X, Y, and Z directions
Shock resistance
150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicatior
Yes (color: green), lighting from 80% to 90% or more of rated voltage
Others
EMI
Conducted Emission Conforms to EN61204-3 EN55011 Class B and based on FCC Class A
Radiated Emission Conforms to EN61204-3 EN55011 Class B
EMS
Conforms to EN61204-3 high severity levels
Approved Standards
UL Listed: UL508 (Listing, Class2 Output: Per UL1310)
UL UR: UL60950-1 (Recognition)
cUL: CSA C22.2 No.107.1 (Class2 Output: Per CSA C22.2 No.223)
cUR: CSA C22.2 No.60950-1
EN/VDE: EN50178 (=VDE0160), EN60950-1 (=VDE0805)
Lloyd’s standards
Fulfilled Standards
SELV (EN60950-1/EN50178/UL60950-1), PELV (EN60204-1, EN50178),
Safety of Power Transformers (EN61558-2-16)
EN50274 for Terminal parts
Degree of protection
IP20 by EN / IEC60529
SEMI
F47-0706 (200 to 240 VAC)
Weight
150 g
195 g
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*2. For a cold start at 25C. Refer to Engineering Data on page 11 for details.
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range. When adjusting
the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
*4. A characteristic when the ambient operating temperature is between 25 to 70C.
*5. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*6. 90 to 350 VDC’s UL standards are scheduled to obtain certification in June, 2013.
3
datasheet pdf - http://www.DataSheet4U.net/










Скачать PDF:

[ S8VK-G.PDF Даташит ]

Номер в каталогеОписаниеПроизводители
S8VK-GSwitch Mode Power SupplyOmron
Omron
S8VK-G01505Switch Mode Power SupplyOmron
Omron
S8VK-G01512Switch Mode Power SupplyOmron
Omron
S8VK-G01524Switch Mode Power SupplyOmron
Omron

Номер в каталоге Описание Производители
TL431

100 мА, регулируемый прецизионный шунтирующий регулятор

Unisonic Technologies
Unisonic Technologies
IRF840

8 А, 500 В, N-канальный МОП-транзистор

Vishay
Vishay
LM317

Линейный стабилизатор напряжения, 1,5 А

STMicroelectronics
STMicroelectronics

DataSheet26.com    |    2020    |