DataSheet26.com

SDR-960 PDF даташит

Спецификация SDR-960 изготовлена ​​​​«Mean Well» и имеет функцию, называемую «960W Single Output Industrial DIN RAIL».

Детали детали

Номер произв SDR-960
Описание 960W Single Output Industrial DIN RAIL
Производители Mean Well
логотип Mean Well логотип 

3 Pages
scroll

No Preview Available !

SDR-960 Даташит, Описание, Даташиты
960W Single Output Industrial DIN RAIL with PFC Function
SDR-960 series
Features:
ACinput180~264VAConly
130%peakloadcapability
110mmslimdesign
Built-inactivePFCfunctioncompliancetoEN61000-3-2
Highefficiency94%andlowpowerdissipation
Protections:Shortcircuit/Overload/Overvoltage/Overtemperature
Coolingbyfreeairconvection
Built-inconstantcurrentlimitingcircuit
CanbeinstalledonDINrailTS-35/7.5or15
UL508(industrialcontrolequipment)approved
EN61000-6-2(EN50082-2)industrialimmunitylevel
Currentsharingupto3840W(3+1)
Built-inDCOKrelaycontact
100%fullloadburn-intest
3yearswarranty
SPECIFICATION
MODEL
SDR-960-24
SDR-960-48
DC VOLTAGE
RATED CURRENT
24V
40A
48V
20A
CURRENT RANGE
RATED POWER
PEAK CURRENT
0 ~ 40A
960W
52A
0 ~ 20A
960W
26A
OUTPUT
PEAK POWER
Note.6 1248W (3sec.)
RIPPLE & NOISE (max.) Note.2 180mVp-p
VOLTAGE ADJ. RANGE
24 ~ 28V
VOLTAGE TOLERANCE Note.3 ±1.0%
LINE REGULATION
±0.5%
LOAD REGULATION
±1.0%
SETUP, RISE TIME
1000ms, 100ms/230VAC at full load
250mVp-p
48 ~ 55V
±1.0%
±0.5%
±1.0%
HOLD UP TIME (Typ.)
14ms / 230VAC at full load
VOLTAGE RANGE Note.7 180 ~ 264VAC 254 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
PF0.95/230VAC at full load
http://www.DataSheet4U.com/
INPUT
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
94%
6A/230VAC
COLD START 50A / 230VAC
94%
LEAKAGE CURRENT
<3.5mA / 240VAC
OVERLOAD
Normally works within 105 ~ 130% rated output power for more than 3 seconds and then shut down o/p voltage with auto-recovery
after 30 seconds if the peak load condition is removed
Constant current limiting within 130 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage, re-power
PROTECTION
OVER VOLTAGE
OVER TEMPERATURE
on to recover
29 ~ 33V
56 ~ 65V
Protection type : Shut down o/p voltage, with auto-recovery or re-power on to recover
90℃±5(TSW) detect on heatsink of power switch
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
DC OK REALY CONTACT RATINGS (max.) 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
FUNCTION
CURRENT SHARING
Please refer to function manual
WORKING TEMP.
Note.5 -30 ~ +70(Refer to "Derating Curve")
WORKING HUMIDITY
20 ~ 95% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85, 10 ~ 95% RH
TEMP. COEFFICIENT
±0.03%/(0 ~ 50℃)
VIBRATION
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508, TUV EN60950-1 approved
SAFETY & WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
EMC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25/ 70% RH
(Note 4) EMC EMISSION
Note.8 Compliance to EN55022 (CISPR22), EN61204-3 Conduction class B, Radiation class A, EN61000-3-2,-3
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A
MTBF
69.8K hrs min. MIL-HDBK-217F (25)
OTHERS DIMENSION
110*125.2*150mm (W*H*D)
NOTE
PACKING
2.47Kg ; 6pcs/15.8Kg/1.55CUFT
1.AllparametersNOTspeciallymentionedaremeasuredat230VACinput,ratedloadand25ofambienttemperature.
2.Ripple&noisearemeasuredat20MHzofbandwidthbyusinga12"twistedpair-wireterminatedwitha0.1uf&47ufparallelcapacitor.
3.Tolerance:includessetuptolerance,lineregulationandloadregulation.
4.Thepowersupplyisconsideredacomponentwhichwillbeinstalledintoafinalequipment.Thefinalequipmentmustbere-confirmedthatitstillmeets
EMCdirectives.
5.Installationclearances:40mmontop,20mmonthebottom,5mmontheleftandrightsidearerecommendedwhenloadedpermanentlywithfullpower.
Incasetheadjacentdeviceisaheatsource,15mmclearanceisrecommended.
6.3secondspeakpowermax.andtheaverageoutputpowershouldnotexceedtheratepower.
7.Deratingmaybeneededunderlowinputvoltage.Pleasecheckthederatingcurveformoredetails.
8.ConsultMEANWELLfordeploymentofRadiationclassB.
File Name:SDR-960-SPEC 2012-11-07









No Preview Available !

SDR-960 Даташит, Описание, Даташиты
960W Single Output Industrial DIN RAIL with PFC Function
Mechanical Specification
SDR-960 series
Case No.214A Unit:mm
TB1
1
2
3
125.2
1
2
3
4
5
6
TB2
1234
CN205
12 3 4
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
http://www.DataSheet4U.com/
Terminal Pin No. Assignment (TB1)
Pin No. Assignment
1 FG
2 AC/N
3 AC/L
Terminal Pin No. Assignment (TB2)
Pin No. Assignment
1,2,3 DC OUTPUT +V
4,5,6 DC OUTPUT -V
Control Pin (CN205) : DINKLE ECH250R-04P or equivalent
Pin No. Assignment
Mating Housing
Wire Diameter
1 P-(Current Share) DINKLE ESC250V-04P
2 P+(Current Share)
or equivalent
(Including in the
3,4 DC OK Relay Contact
single package)
0.081~0.517mm2
(28~20AWG)
Block Diagram
PFC fosc : 65KHz
PWM fosc : 60KHz
DC OK
EMI FILTER
I/P &
RECTIFIERS
FG
PFC
CIRCUIT
U.V.P.
PFC
CONTROL
DC OK Relay Contact
Contact Close
PSU turns on / DC OK.
Contact Open
PSU turns off / DC Fail.
Contact Ratings (max.) 30V/1A resistive load.
POWER
SWITCHING
O.L.P.
O.T.P.
PWM & PFC
CONTROL
RECTIFIERS
&
FILTER
O.C.P.
DETECTION
CIRCUIT
CURRENT SHARE
O.V.P.
+V
-V
CURRENT
SHARE
File Name:SDR-960-SPEC 2012-11-07









No Preview Available !

SDR-960 Даташит, Описание, Даташиты
960W Single Output Industrial DIN RAIL with PFC Function
Peak Loading
(1)
1248W
(2)
1248W
SDR-960 series
960W
50 sec. 3 sec.
480W
15 sec. 3 sec.
Derating Curve
Output derating VS input voltage
130
100
80 For 3 sec. (typ.) Continuous
60
40
20
100
90
80
70
60
50
40
-30 0 10 20 30 40 50 60 70 (VERTICAL)
AMBIENT TEMPERATURE ()
180 190 200 210 220 230 240 250 264
INPUT VOLTAGE (V) 60Hz
Function Manual
1. Current sharing
http://www.DataSheet4U.com/
(1) Parallel operation is available by connecting the units shown as below (P+,P- are connected mutually in parallel).
(2) Difference of output voltages among parallel units should be less than 0.2V.
(3) The total output current must not exceed the value determined by the following equation (Output current at parallel operation)=(The rated current per unit) x (Number of unit) x 0.9.
(4) In parallel operation 4 units is the maximum, please consult the manufacture for other applications.
(5) The power supplies should be paralleled using short and large diameter wiring and then connected to the load.
(6) When in parallel operation, the minimum output load should be greater than 5% of total output load.
(Min. load >5% rated current per unit x number of unit)
(7) In parallel connection, maybe only one unit (master) operate if the total output load is less than 5% of rated load condition.
The other PSUs (slaves) may go into standby mode and their output LEDs & relays will not turn on.
(8) Some minor noise may be heard at light load condition under parallel operation.
This is a normal phenomenon and the performance of the PSU will not be influenced.
PSU PSU
TB2
-V +V
CN205
1 P-
2 P+
3 DC OK
4 DC OK
P-(pin1)
P+(pin2)
TB2
-V +V
CN205
1 P-
2 P+
3 DC OK
4 DC OK
PSU
TB2
-V +V
CN205
1 P-
2 P+
3 DC OK
4 DC OK
-V +V
LOAD
PSU
TB2
-V +V
CN205
1 P-
2 P+
3 DC OK
4 DC OK
P+ and P- lines
should be twisted in pairs
File Name:SDR-960-SPEC 2012-11-07










Скачать PDF:

[ SDR-960.PDF Даташит ]

Номер в каталогеОписаниеПроизводители
SDR-960960W Single Output Industrial DIN RAILMean Well
Mean Well

Номер в каталоге Описание Производители
TL431

100 мА, регулируемый прецизионный шунтирующий регулятор

Unisonic Technologies
Unisonic Technologies
IRF840

8 А, 500 В, N-канальный МОП-транзистор

Vishay
Vishay
LM317

Линейный стабилизатор напряжения, 1,5 А

STMicroelectronics
STMicroelectronics

DataSheet26.com    |    2020    |