Número de pieza | HAS300-P | |
Descripción | Current Transducers HAS 50~600-P | |
Fabricantes | LEM | |
Logotipo | ||
Hay una vista previa y un enlace de descarga de HAS300-P (archivo pdf) en la parte inferior de esta página. Total 2 Páginas | ||
No Preview Available ! Current Transducers HAS 50..600-P
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 50..600 A
VOUT = ±4 V
Electrical data
Primary nominal
r.m.s. current
IPN (A)
50
100
200
300
400
500
600
Primary current
measuring range
IP (A)
±150
±300
±600
±900
±900
±900
±900
Type
HAS 50-P
HAS 100-P
HAS 200-P
HAS 300-P
HAS 400-P
HAS 500-P
HAS 600-P
VC
IC
I
OC
Vd
V
b
RIS
VOUT
ROUT
R
L
Supply voltage (± 5 %)
±15
Current consumption
±15
Overload capacity
30,000
R.m.s. voltage for AC isolation test, 60 Hz, 1 mn 3
R.m.s. rated voltage, safe separation
5001)
Isolation resistance @ 500 VDC
> 1000
Output voltage @ ± IPN, RL = 10 kΩ, TA = 25°C
±4V ±40
Output internal resistance
approx. 100
Load resistance
>1
V
mA
At
kV
V
MΩ
mV
Ω
kΩ
Accuracy - Dynamic performance data
X
εL
VOE
V
OH
VOT
εTC G
tr
di/dt
f
Accuracy @ IPN, TA = 25°C (without offset)
Linearity 2) (0 .. ± IPN)
Electrical offset voltage, TA = 25°C
Hysteresis offset voltage @ IPN→ 0
Thermal drift of VOE HAS 50-P
HAS 100..600-P
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
di/dt accurately followed
Frequency bandwidth (small signal, -1dB) 3) 4)
< ±1
%
< ±1 % of IPN
< ±40
mV
< ±20
mV
< ±2 mV/K
< ±1 mV/K
< ±0.1 %/K
< 3 µs
> 50
A/µs
DC .. 25 kHz
General data
TA Ambient operating temperature
TS Ambient storage temperature
m Mass
Standards 5)
- 25 .. + 85 °C
- 25 .. + 85 °C
approx. 80
g
EN 50082-2
Notes : 1) Pollution class 2, overvoltage category III.
2) Linearity data exclude the electrical offset.
3) Please refer to derating curves in the technical file to avoid excessive
core heating at high frequency.
4) Amorphous core option for high frequency application.
5) Please consult characterisation report for more technical details and
application advice.
Features
• Hall effect measuring principle
• Galvanic isolation between primary
and secondary circuit
• Isolation voltage 3000 V~
• Low power consumption
• Extended measuring range (3 x IPN)
• Insulated plastic case made of
polycarbonate PBT recognized
according to UL 94-V0
• Right angle pins for direct PCB
mounting
Advantages
• Easy mounting
• Small size and space saving
• Only one design for wide current
ratings range
• High immunity to external
interference.
Applications
• AC variable speed drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Switched Mode Power Supplies
(SMPS)
• Power supplies for welding
applications.
040406/0
LEM Components
www.lem.com
1 page |
Páginas | Total 2 Páginas | |
PDF Descargar | [ Datasheet HAS300-P.PDF ] |
Número de pieza | Descripción | Fabricantes |
HAS300-P | Current Transducers HAS 50~600-P | LEM |
HAS300-S | Current Transducers HAS 50 to 600-S | LEM |
Número de pieza | Descripción | Fabricantes |
SLA6805M | High Voltage 3 phase Motor Driver IC. |
Sanken |
SDC1742 | 12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters. |
Analog Devices |
DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares, |
DataSheet.es | 2020 | Privacy Policy | Contacto | Buscar |