DataSheet26.com

6SL3131-7TE28-0AA3 PDF даташит

Спецификация 6SL3131-7TE28-0AA3 изготовлена ​​​​«Siemens» и имеет функцию, называемую «Active Line Modules in booksize format».

Детали детали

Номер произв 6SL3131-7TE28-0AA3
Описание Active Line Modules in booksize format
Производители Siemens
логотип Siemens логотип 

12 Pages
scroll

No Preview Available !

6SL3131-7TE28-0AA3 Даташит, Описание, Даташиты
© Siemens AG 2007
SINAMICS S120 drive system
Booksize format for Line and Motor Modules
Active Line Modules in booksize format
Overview
Design (continued)
The scope of supply of the Active Line Modules includes:
• DRIVE-CLiQ cable for connection to the Control Unit for drive
control on the immediate left
• DRIVE-CLiQ cable (length depends on module width) to
connect Active Line Module to adjacent Motor Module
• 2 blanking plugs for sealing unused DRIVE-CLiQ sockets
• Jumper for connecting the 24 V DC busbar to the adjacent
Motor Module
• 24 V terminal adapter
• Connector X21 for digital inputs
• Fan insert for the 80 kW (100 HP) and 120 kW (150 HP) Active
Line Modules is supplied with the modules. The voltage for the
fan insert is supplied by the Active Line Module.
• 1 set of warning signs in foreign languages
Integration
The self-commutated feed/feedback units (with IGBTs in infeed
and regenerative feedback directions) generate a regulated DC
link voltage. This means that the connected Motor Modules are
decoupled from the line voltage. Line voltage fluctuations within
the permissible supply tolerances have no effect on the motor
voltage. Active Line Modules are designed for connection to
grounded-neutral (TN, TT) and non-grounded (IT) supply
systems.
The Active Line Module communicates via DRIVE-CLiQ with the
CU320 Control Unit, SINUMERIK 802D sl,
SINUMERIK 840D sl with NCU 710.1/NCU 720.2/NCU 730.1/
NCU 730.2 PN or with the Numeric Control
Extensions NX10/NX15 and receives its control information from
these sources.
The DC link is pre-charged via integrated precharging resistors.
In order to operate an Active Line Module, it is absolutely
essential to use the appropriate Active Interface Module or
matching line reactor.
Design
The Active Line Modules in booksize format feature the following
interfaces as standard:
• 1 line connection via screw-type terminals
• 1 connection for the 24 V DC electronics power supply via the
24 V terminal adapter included in the scope of supply
• 1 DC link connection via integrated DC link busbars
• 3 DRIVE-CLiQ sockets
• 2 PE (protective earth) connections
The status of the Active Line Modules is indicated via two
multi-color LEDs.
On the 100 mm (3.94 in) wide Active Line Module, the shield for
the power supply cable can be connected to the integrated
shield connection plate via a shield connection terminal or tube
clip, e.g. Weidmüller type KLBÜ CO 4. The shield connection
terminal must not be used for strain relief. Shield connection
plates are available for the 150 mm (5.91 in), 200 mm (7.87 in)
and 300 mm (11.81 in) wide modules.
The signal cable shield can be connected to the Line Module by
means of a shield connection terminal, e.g. type KLBÜ 3-8 SC
by Weidmüller.
9
Siemens NC 61 · 2007/2008
9/35









No Preview Available !

6SL3131-7TE28-0AA3 Даташит, Описание, Даташиты
© Siemens AG 2007
SINAMICS S120 drive system
Booksize format for Line and Motor Modules
Active Line Modules in booksize format
Technical specifications
General technical specifications
Line connection voltage
Up to 2000 m (6562 ft) above sea
level
Line frequency
Power factor
• Active mode
- Fundamental power factor
(cos ϕ1)
- Total (λ)
• Smart mode
- Fundamental mode
- Total
DC link voltage Vd
Electronics power supply
380 ... 480 V 3 AC ± 10%
(-15% < 1 min)
47 … 63 Hz
1.0 (factory setting), can be
altered by input of a reactive
current setpoint
1.0 (factory setting)
> 0.96
0.65 … 0.90
In Active Mode, the DC link
voltage is regulated and can be
adjusted as a voltage decoupled
from the line voltage.
In Smart Mode, the DC link
voltage is regulated in proportion
to the line voltage to the mean
rectified line voltage value.
Factory setting for DC link
voltage:
380 ... 400 V 3 AC: 600 V
(Active Mode)
400 ... 415 V 3 AC: 625 V
(Active Mode)
416 ... 480 V 3 AC: 1.35 x line
voltage (Smart Mode)
24 V DC -15%/+20%
General technical specifications (continued)
Type of cooling
Internal air cooling, power units
with increased air cooling pro-
vided by integrated fan
Built-on fan (with 80 kW (100 HP)
and 120 kW (150 HP) Active Line
Modules).
Permissible ambient or coolant
temperature (air)
in operation for line-side compo-
nents, Line Modules and Motor
Modules
0 ... 40 °C (32 ... 104 °F) without
derating,
> 40 ... 55 °C (104 ... 131 °F),
see derating characteristics
Installation altitude
Up to 1000 m (3281 ft) above
sea level without derating,
> 1000 ... 4000 m (3281 ...
13124 ft) above sea level,
see derating characteristics
Conformity
CE (low-voltage and EMC
directives)
Approvals
cULus (File No.: E192450)
Radio interference suppression
• Active Line Module 16 kW (18 HP)
and 36 kW (40 HP)
- Standard (Active Line Module + no radio interference suppression
line reactor)
- with line filter package
Class A1 to EN 55011 and
Category C2 to EN 61800-3
• Active Line Module
55 kW (60 HP), 80 kW (100 HP)
and 120 kW (150 HP)
- Standard (Active Line Module + Category C3 to EN 61800-3 up to
Active Interface Module)
350 m (1148 ft) total cable length
- with Basic Line Filter
9
Class A1 to EN 55011 and Cate-
gory C2 to EN 61800-3 up to
350 m (1148 ft) total cable length
Category C3 to EN 61800-3 from
350 m to 1000 m (1148 ft to
3281 ft) total cable length
9/36
Siemens NC 61 · 2007/2008









No Preview Available !

6SL3131-7TE28-0AA3 Даташит, Описание, Даташиты
© Siemens AG 2007
SINAMICS S120 drive system
Booksize format for Line and Motor Modules
Active Line Modules in booksize format
Technical specifications (continued)
Line voltage 380 ... 480 V 3 AC
Order No.
• Internal air cooling
• External air cooling
Product name
6SL3130-
7TE21-6AA3
6SL3130-
7TE23-6AA3
6SL3130-
7TE25-5AA3
6SL3131-
6SL3131-
6SL3131-
7TE21-6AA3
7TE23-6AA3
7TE25-5AA3
Active Line Modules in booksize format
6SL3130-
7TE28-0AA3
6SL3131-
7TE28-0AA3
6SL3130-
7TE31-2AA3
6SL3131-
7TE31-2AA3
Feed/feedback power
Rated
- with
3p8o0wVer3PAraCted
kW 16
36
55
80
120
- with 460 V 3 AC4)
(HP)
(18)
(40)
(60)
(100)
(150)
for S6 duty (40%)
Pmax
Pmax,
maximum
PS6
kW 21
kW 35
kW 27
47
70
60
71
91
92
106 158
131 175
134 200
DC link current
• at 600 V DC
• for S6 duty (40%)
V 35
A 59
79 121 176 244
117 152 218 292
Input current
• Rated current
at 380 V 3 AC
• for S6 duty (40%)
• Maximum
Current requirement
24 V DC electronics power
supply, max.
A
A
A
A
26
35
59
1.1
58 88 128 192
79 121 176 244
117 152 195 292
1.5 1.9 2.0 2.5
Current capacity
• of 24 V DC busbars
A 20
20
20
20
20
• DC link busbars A 100 200 200 200 200
DC link capacitance
• Smart Line Module
• Drive group, max.
μF
μF
Efficiency η
Power loss1)
• with internal air cooling
kW
• with external air cooling int./ext. kW
Cooling air requirement
m3/s (ft3/s)
Sound pressure level
dB (A)
Line connection
U1, V1, W1
• Conductor cross-section
Shield connection
mm2
PE connection
710
20000
0.98
0.26
0.06/0.2
0.016 (0.565)
< 60
Screw-type
terminals (X1)
2.5 ... 10
Integrated into the
connector
On housing with
M5 screw
1410
20000
0.98
0.63
0.135/0.495
0.031 (1.095)
< 65
M6 screw studs for
ring terminal ends
(X1)
2.5 ... 50
See Accessories
On housing with
M6 screw
1880
20000
0.98
0.90
0.2/0.7
0.044 (1.554)
< 60
M8 screw studs for
ring terminal ends
(X1)
2.5 ... 95, 2 x 35
See Accessories
On housing with
M6 screw
2820
20000
0.98
1.35
0.305/1.045
0.144 (5.085)
< 75
M8 screw studs for
ring terminal ends
(X1)
2.5 ... 120, 2 x 50
See Accessories
On housing with
M8 screw
3995
20000
0.98
2.20
0.49/1.71
0.144 (5.085)
< 75
M8 screw studs for
ring terminal ends
(X1)
2.5 ... 120, 2 x 50
See Accessories
On housing with
M8 screw
Cable length, max.
(total of all motor cables
and DC link)
• Shielded
• Unshielded
Degree of protection
m (ft)
m (ft)
35560033))
(1150)
(1840)
IP20
35560033))
(1150)
(1840)
IP20
1000 (3281)
1500 (4922)
IP20
1000 (3281)
1500 (4922)
IP20
1000 (3281)
1500 (4922)
IP20
Dimensions
• Width
• Height
mm (in)
mm (in)
• Depth
- with internal air cooling
- with external air cooling
on/behind mounting surface
mm (in)
mm (in)
100 (3.94)
380 (14.96)
150 (5.91)
380 (14.96)
270 (10.63)
270 (10.63)
226/66.5 (8.9/2.6) 226/71 (8.9/2.8)
200 (7.87)
380 (14.96)
270 (10.63)
226/92 (8.9/3.6)
300 (11.81)
380,
with
f(a1n42.)9: 6)
629 (24.8)
270 (10.63)
226/82 (8.9/3.2)
300 (11.81)
380,
with
f(a1n42.)9: 6)
629 (24.8)
270 (10.63)
226/82 (8.9/3.2)
Weight
• with internal air cooling,
approx.
• with external air cooling,
approx.
kg (lb)
kg (lb)
7 (15)
8.8 (19)
10.3 (23)
13.8 (30)
17 (38)
18.5 (41)
23 (51)
27.7 (61)
23 (51)
30.7 (68)
9
1) Power loss of Active Line Module at rated power without losses of 24 V DC electronics power supply.
2) The fan is supplied with the Active Line Module and must be installed before the Active Line Module is commissioned.
3) Max. cable lengths in conjunction with HFD line reactors, see derating characteristics.
4) Nominal HP ratings are provided for ease of assigning components only. The Line Module power is dependent on the Motor Module loading
and is to be dimensioned accordingly.
Siemens NC 61 · 2007/2008
9/37










Скачать PDF:

[ 6SL3131-7TE28-0AA3.PDF Даташит ]

Номер в каталогеОписаниеПроизводители
6SL3131-7TE28-0AA3Active Line Modules in booksize formatSiemens
Siemens

Номер в каталоге Описание Производители
TL431

100 мА, регулируемый прецизионный шунтирующий регулятор

Unisonic Technologies
Unisonic Technologies
IRF840

8 А, 500 В, N-канальный МОП-транзистор

Vishay
Vishay
LM317

Линейный стабилизатор напряжения, 1,5 А

STMicroelectronics
STMicroelectronics

DataSheet26.com    |    2020    |

  Контакты    |    Поиск